On HomeDepot's site I found :
"IDEAL 4-in-1 200 Amp Test Tool Model 61-702"
Would this be what you guys are refering too?
The plan is to run dedicated circuits but in the mean time I wanted to distribute the load a bit.. cause as it is now we have no margin.. We have like one outlet in the entire house we can plug the vaccuum into.. I really need to figure out every outlet is on what breaker also that would probobly help as well..My dad mentioned that lighting circuits normally use 15amp breakers and outlet circuits use 20amp but from what he recalls uses the same guage wire.. About a year ago most of the breakers where switched to 15amp from what I was told.. Is what my dad mentioned correct? Could we upgrade them to 20's and be ok? Or since how old the wires are should they be left at 15? As for the house surge protector that would be cool but considering we have like 3 ups units and surge protectors everywhere I think we should be ok that way, will mention it though and see how hard it would be to put something like that in here. Thanks for the replies!